Mts Model FlexTest SE Manual do Utilizador Página 78

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 264
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 77
Models FlexTest® IIm/GT/SE Controller Hardware
Specifications–UPS Systems Used with MTS
Installation
78
The addition of a low battery warning relay contact out from the UPS will
provide additional system safety protection by letting the controller know that the
UPS battery is low.
Specifications–UPS Systems Used with MTS Controllers
Any UPS used with an MTS system must comply with these specifications.
UPS power
requirements
The following UPS power requirements include power for the PC, MTS
Controller (one chassis), and 25% capability for other subsystems.
UPS Specifications
I
TEM REQUIREMENT
Operating temperature 5–40 deg C
Operating humidity 5–85% non-condensing
Supported UPS output
voltage range
100–240 V AC nominal, single phase,
sine-wave output
Input/output frequency
range
50–60 Hz
Output load regulation -/+5% nominal operating voltage (both in
battery and normal operation modes)
Switch-over time to battery
on power loss
0 s (recommended), < 6 ms (required)
UPS Power Requirements
C
ONTROLLER TYPE CONTROLLER CHASSIS UPS POWER REQUIRED
FlexTest SE 493.02 1200 watt
FlexTest GT 493.10 2500 watt
Aero ST 493.20 3500 watt
Flextest 40 494.04 1200 watt
FlexTest 60 494.06 1800 watt
FlexTest 100 494.10 2500 watt
FlexTest 200 494.20 3500 watt
Vista de página 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 263 264

Comentários a estes Manuais

Sem comentários