Cabling and Programming Series 407 Controllers
Models FlexTest® IIm/GT/SE Controller Hardware FlexTest GT Controller Connections
151
Cabling and Programming Series 407 Controllers
This section describes:
Cabling and programming the FlexTest GT Controller to analog program
and feedback signals from a Series 407 Controller.
Connecting FlexTest GT Controllers to interlock signals from a Series 407
Controller.
Setting up a Series 407 Controller to send and receive signals from FlexTest
GT Controllers.
Important When used as a programmer, FlexTest GT Controllers do not have
automated mode switching capabilities. Control mode selection on
these controllers do not effect the control mode of the controller to
which they are sending test commands.
How to Provide Program to a Series 407 Controller
1. Cable the Series Series 793 and Model 407 Controllers together.
Cable the analog inputs and outputs between the Model 493.10 chassis and a
Model 407 Controller as follows:
Note Analog I/O connectors are located on the rear panel of the chassis.
A. Connect a Model 493.76 Analog Out BNC connector to the program
(analog) input on the 407 Controller. Connections for single or multiple
Model 407 Controllers are shown.
B. If you intend to monitor sensor feedback for data acquisition or control
feedback, connect the external controllers conditioner output to a
Model 493.77 Filtered Analog Input BNC connector. For conditioner
output locations on various MTS devices, see “Miscellaneous
Conditioner Output Connections” on page 167.
C. Make interlock connections as appropriate. See “Connecting Interlock
Signals to 407 Controllers” on page 156.