Models FlexTest® IIm/GT/SE Controller Hardware
J55 Digital Outputs
FlexTest SE Controller Connections
238
Stand-alone mode
1. Press Setup on the console front panel menu.
2. Scroll down the Setup menu to Digital Output 1.
3. Press the button next to Digital Output 1.
4. Press the button next to Assignment until the state Run/Stop is shown.
5. Press Polarity to select Normal or Inverted.
Automation mode
1. Ensure that digital outputs have been added using Station Builder.
2. In the Station Manager window’s Display menu, select Station Setup.
3. In the Station Setup window’s navigation pane, double-click Digital
Inputs/Outputs and then click Outputs.
4. On the Digital Outputs window, use Assignment for Digital Output 1 to
assign Run/Stop.
5. Use Polarity to select the required polarity (Normal or Inverted) for
Digital Output 1.